Wire size · NEC 2023

Can I use 14 gauge wire on a 20-amp breaker?

No, not in general240.4(D) limits 14 AWG copper to a 15-amp breaker, unless 240.4(E) or 240.4(G) specifically permits otherwise.

Why it isn't allowed

Table 310.16 shows 14 AWG copper at 20 A in the 75°C column, which makes it look fine. But 240.4(D) sets a separate limit on the breaker size for small conductors.

Size60°C75°CNote
14 AWG copper15 A20 A240.4(D) limit: 15 A
12 AWG copper20 A25 A240.4(D) limit: 20 A

What to do instead

The exceptions

240.4(D) opens with "unless specifically permitted in 240.4(E) or 240.4(G)". Those sections cover specific cases, so confirm yours is listed before relying on them.

General guidance for a typical circuit under NEC 2023. Ambient temperature, bundling, terminations and local amendments can change the result. Check the code adopted in your area and your local inspector. Spot an error? Email contact@twoscripts.com.