What size wire for 50 amps?

6 AWG copper6 AWG copper, rated 55 A at 60°C, is the safe default for a 50-amp circuit. 8 AWG works only where the 75°C column applies.

Why 6 AWG

Terminations matter here. Under 110.14(C), circuits of 100 A or less use the 60°C column unless the equipment is listed and identified for higher-temperature conductors. Above 100 A, the 75°C column applies.

Size60°C75°CNote
8 AWG copper40 A50 AOnly with 75°C-rated terminations
6 AWG copper55 A65 AWorks in either column

When 8 AWG copper is allowed

8 AWG reaches 50 A in the 75°C column only. Use it only if the equipment at both ends is listed and identified for it. If you can't confirm that, use 6 AWG.

What about aluminum?

Use 4 AWG aluminum or copper-clad aluminum, rated 55 A at 60°C. 6 AWG aluminum reaches 50 A at 75°C only, under the same termination rule.

Ground wire

Table 250.122 gives a minimum 10 AWG copper equipment grounding conductor for a 50-amp breaker.

Long runs: check voltage drop

A 50 A load, 100 ft one way, on 240 V single-phase, with 6 AWG copper drops about 4.9 V, or 2.0%. Longer runs may need a larger wire.

Worked with VD = 2 × K × I × L ÷ cmil, using K = 12.9 for copper.

General guidance for a typical circuit under NEC 2023. Ambient temperature, bundling, terminations and local amendments can change the result. Check the code adopted in your area and your local inspector. Spot an error? Email contact@twoscripts.com.